Grease that gets past the canopy filters settles inside the ductwork. Left there, it is fuel. A flare-up on the cooking line can travel into the duct and through the building. That is why kitchen extraction cleaning frequency is something insurers ask about, and why there is a recognised standard for it.
The standard: TR19 Grease
TR19 Grease is the BESA specification for fire risk management of grease in kitchen extraction systems. It sets out how often a system should be cleaned, how clean it should be afterwards and what the cleaning contractor should record.
How often: the TR19 intervals
The interval is based on how many hours a day the kitchen cooks:
- Heavy use, 12 to 16 hours a day: every 3 months
- Moderate use, 6 to 12 hours a day: every 6 months
- Light use, 2 to 6 hours a day: every 12 months
These are starting points. The type of cooking matters as much as the hours. Chargrills, woks and fryers produce far more grease than ovens and steamers, so a kitchen with heavy frying may need cleaning sooner than its hours suggest. Your insurer may also set its own interval in the policy, and that is the one you will be held to.
What should be cleaned
A proper clean covers the whole grease path: the canopy and its plenum, the ductwork from end to end, the fan and the discharge point. Cleaning only the parts that are easy to reach is the most common shortfall, and it leaves the highest-risk sections untouched.
Records to keep
- A report with before and after photographs
- Grease thickness readings taken before and after
- A note of any section that could not be reached, and why
- A certificate with the date and the next clean due
If a section could not be reached, the answer is usually an extra access door, not a longer brush.
What the kitchen team does in between
Canopy filters need cleaning far more often than the ductwork, weekly or more in a busy kitchen. Clean filters catch more grease, which keeps the duct cleaner for longer.
Designing for cleaning
Systems are much cheaper to keep clean when access was planned at the start. When we build extraction systems we fit access doors at the intervals the cleaning standard expects and hand over a schedule showing where they are. If your current system is hard to clean, we can often add access to the existing ductwork. Ask us to take a look.
This article is general guidance. Check your insurance policy for the interval that applies to you.